主營:消火栓泵、消防(fang)穩壓設備(bei)、變頻無負(fu)壓供水設備(bei)
product display
消防穩壓設備根據穩壓系統設置的方式的不同可分為:高位水箱自然穩壓、穩壓泵系統設置在屋頂的穩壓系統、穩壓泵系統設置在消防泵房的穩壓系統。
一、高位水箱自然穩壓
設置原則:高位水箱的設置高度應保證不利點消火栓靜水壓力,當建筑高度不超過100m時,高層建筑不利點消火栓靜水壓力不應低于0.07mpa;當建筑高度超過100m時,高層建筑不利點消火栓靜水壓不應低于0.15mpa;噴淋系統必須保證不利點噴頭的工作壓0.1mpa。
高位水(shui)箱穩壓是利用水(shui)的重力(li)流供(gong)水(shui)的系統,一般(ban)設置(zhi)在建筑(zhu)物的高處或(huo)臨近(jin)高層建筑(zhu)的頂部(bu)。
二、帶穩壓泵的穩壓系統(設置在屋頂)
設置原則:高位水箱設置于建筑物樓頂或建筑群的箱泵一體化相對高樓的樓頂,保證系證水壓同上所描述。
此種設置又存在兩種情況:
①住宅與商業、辦公混建或純住宅的情況,這樣商業、辦公一般設于較低層,而住宅部分一般聯設置噴淋系統,此情況下,穩壓水箱設于樓頂完全可滿足噴淋系統不利點工作壓力,這樣的話我們只需要設置一套穩壓泵(一用一備)就足夠了,噴淋系統無需在另設穩壓泵。
②純辦公、純商業或辦公商業混建的情況,這種情況可能頂層也需要設置噴淋系統,穩壓水箱設置于頂層就不能在滿足噴淋系統不利點工作壓力要求了,我們需要加一套噴淋穩壓泵(一用一備)。
以上兩種穩壓泵胡設置是我們施工過程中常見的穩壓泵設置形式。
三、帶穩壓泵的穩壓系統(設置于地下消防泵房內)
設置原則:兩套穩壓泵(消火栓一套,噴淋一套都設置在消防水泵房內)
這種設置方法優點就在于不用在設置高位水箱了,消防穩壓設備系統直接從消防水池吸水即可,但是也存在其缺點
①需要水泵房內空間加大,為穩壓系統預留空間。
②穩壓泵的相應的參數需要增加。
此情況氣壓罐取代(dai)了高(gao)位(wei)水箱的作用(yong),一般不(bu)適合高(gao)層建(jian)筑的穩壓。當建(jian)筑高(gao)度(du)不(bu)超過24m時(shi),此種設置(zhi)方(fang)式還(huan)是比(bi)較適合的。
消防穩壓設備特點:
設備與消防控制中心聯動,火警時自動進入消防狀態,并備有聯動反饋接口,控制消防泵的啟動可以采用工頻直接起動,自耦降壓啟動,星三角降壓啟動等方式,以滿足不同的使用要求。
消防控制具有過壓,欠壓,過流,短路,缺相,水源缺水等故障報警與保護功能,消防控制主備泵擁有互為備用功能,主泵具有互為備用功能,主泵故障時備用泵自動投入工作。
電源切換功能:
可(ke)(ke)根據(ju)需要(yao)加裝(zhuang)雙電(dian)(dian)(dian)(dian)(dian)(dian)源切(qie)換功(gong)(gong)能(neng),或(huo)另配(pei)單獨的雙電(dian)(dian)(dian)(dian)(dian)(dian)源切(qie)換柜,主(zhu)備電(dian)(dian)(dian)(dian)(dian)(dian)源能(neng)夠自(zi)動(dong)(dong)或(huo)手動(dong)(dong)切(qie)換,主(zhu)電(dian)(dian)(dian)(dian)(dian)(dian)源停電(dian)(dian)(dian)(dian)(dian)(dian)時,備用電(dian)(dian)(dian)(dian)(dian)(dian)源停電(dian)(dian)(dian)(dian)(dian)(dian)時,備用電(dian)(dian)(dian)(dian)(dian)(dian)源自(zi)動(dong)(dong)投入,主(zhu)電(dian)(dian)(dian)(dian)(dian)(dian)源恢(hui)復(fu)供(gong)電(dian)(dian)(dian)(dian)(dian)(dian)時,備用電(dian)(dian)(dian)(dian)(dian)(dian)源自(zi)動(dong)(dong)退出,可(ke)(ke)根據(ju)用戶要(yao)求配(pei)備工頻自(zi)動(dong)(dong)巡檢功(gong)(gong)能(neng)或(huo)低頻自(zi)動(dong)(dong)巡檢功(gong)(gong)能(neng),巡檢時主(zhu)泵(beng)(beng)逐(zhu)臺啟動(dong)(dong)運(yun)行,有故障(zhang)停泵(beng)(beng)報(bao)警,以避免消(xiao)防泵(beng)(beng)長期不運(yun)行而產生的軸承銹蝕,電(dian)(dian)(dian)(dian)(dian)(dian)機受潮葉輪卡死等故障(zhang),保證(zheng)設(she)備處于完(wan)好(hao)狀態,巡檢過程中接到消(xiao)防信號自(zi)動(dong)(dong)退出巡檢時自(zi)動(dong)(dong)開閥泄(xie)水(shui),以保證(zheng)消(xiao)防管網不超壓,消(xiao)防設(she)備還可(ke)(ke)以增設(she)自(zi)動(dong)(dong)控制[BA]接口,與終端計算機聯網,實(shi)現(xian)計算機遠(yuan)程監控。